PILZ

    Out Of Stock

    328150

    PSS u2, electronic module, failsafe, digital inputs and outputs, 2 outputs, relay contacts, N/O, to switch resistive and inductive loads, max. 250 V AC 10 A (AC1), volt-free, switch-off delay configurable, protective coding PSS u2 A CE T available for terminal block, 2-row, terminal block PSS u2 T 8 required (not supplied with the system).


    $430.81 $359.01 / each
    166475
    328150
    PILZ
    FACTORY SEALED
    328150.pdf

    • Quality Assurance

      OEM Quality Spare Parts.

    • Secure Shopping

      100% Money Back Guarantee.

    • 30-DAY RETURNS

      30 Days After-sales Return.

    • Worldwide Delivery

      Worldwidely Fast Shipping.


    ApprovalCE  
    cULus Listed  
    TÜV  
    Application rangeFailsafe  
     
    Technical data
    Potential isolation U2Yes  
    Permitted loadsResistive  
    Inductive  
    Number of relay outputs2  
    Utilisation cat. AC/DC1 stand.EN 60947-4-1  
    Voltage AC1 safety cont.250  V
    Max. current AC1 safety cont.10  A
    Voltage DC1 safety cont.24  V
    Max. current DC1 safety cont.10  A
    Utilisation cat. AC15/DC13sta.EN 60947-5-1  
    Voltage AC15 safety cont.230  V
    Max. current AC15 safety cont.3  A
    Voltage DC13 safety cont.24  V
    Safety contacts: AC at UL250 VAC G.U. (same polarity)  
    Safety contacts: pilot dutyB300, R300  
    Relay contact materialAgCuNi  
    Addit. contact details relay+ 0.2 µm Au  
    Pot. isolation relay outputsYes  
    Climatic suitability to ...EN 60068-2-30  
    EN 60068-2-2  
    EN 60068-2-1  
    EN 60068-2-78  
    EN 60068-2-14  
    Ambient temperature standardEN 60068-2-14  
    Ambient temperature0 - 60  °C
    Storage temperature standardEN 60068-2-1/-2  
    Climatic suitability standardEN 60068-2-78  
    Humidity rating93 % r. h. at 40 °C  
    Condensation permitted?Not permitted  
    Perm. operating height ASL2000 m  
    EMC to standard ...EN 61131-2 (Zone B)  
    Vibration to standard ...EN 60068-2-6  
    Acc. shock to standard1150 m/s²  
    Clearance & creepage dist.to 2EN 60664-1  
    Overvoltage category 2III  
    Clearance & creepage dist. toEN 61131-2  
    UL/IEC 61010-2-201  
    Overvoltage categoryII  
    Pollution degree clear.&creep.2  
    Protection type standardEN 60529  
    Protection type, mounting 
    Protection type, housing 
    Potential isolation 1 betweenRL output and RL output  
    Type of potential isolation 1Safe separation  
    Potential isolation 2 betweenRL output and periphery supply  
    Type of potential isolation 2Safe separation  
    Potential isolation 3 betweenRL output and module supply  
    Type of potential isolation 3Safe separation  
    Potential isolation 4 betweenPeriphery and module supply  
    Type of potential isolation 4Functional insulation  
    Housing materialPC  
    Terminal styleplug-in  
    Height dimension110.8  mm
    Width dimension25  mm
    Depth dimension72.5  mm
    Net weight93  g
    Gross weight110  g
    REACh compliancecontains min. 1 SVHC-substance  
    WEEE classifikation (08/2018)5 devices (feed size < 50cm>
    ECLASS versionECLASS-9.1  
    ECLASS Reference Feature27242604  
    ETIM VersionETIM-7.0  
    ETIM Reference GroupEG000024  

    The exact weight of the cargo you've scheduled will be measured at the QUANTUM office. We will send you an email with a payment link if the weight difference is larger than the shipment amount. The payment link email will include the new weight and the difference amount that must be paid. If you have any queries concerning this procedure, please contact our customer support team at +1-905-625-3500.

    My Rating

    Login to add/edit rating

    You Have To Buy The Product To Give A Review

    All Ratings


    No Ratings Yet
    Quatum First Automation

    Not Getting The Products Which You Are Searching For?

    We currently stock or can Source at a very competitive price 

    Contact Us Today
    Live Chat Support